Quick Answer
A 120-volt, 20-amp copper circuit with a 50-foot one-way run needs approximately 10 AWG wire to stay within the 3% voltage drop recommendation.
Common Examples
| Input | Result |
|---|---|
| 120V, 20A, 50 ft, 3%, copper | 10 AWG (approximately 2.07% drop) |
| 120V, 15A, 75 ft, 3%, copper | 10 AWG (approximately 2.33% drop) |
| 240V, 40A, 100 ft, 3%, copper | 8 AWG (approximately 2.60% drop) |
| 120V, 20A, 50 ft, 3%, aluminum | 8 AWG (approximately 2.14% drop) |
| 120V, 20A, 100 ft, 3%, copper | 8 AWG (approximately 2.60% drop) |
How It Works
This calculator uses the standard voltage drop formula for single-phase circuits, solved in reverse:
VD = (2 x K x I x L) / CM
Where:
- VD = voltage drop in volts
- K = resistivity constant of the conductor material in ohm-cmil/ft. For copper, K = 12.9. For aluminum, K = 21.2.
- I = load current in amperes
- L = one-way length of the wire run in feet (the formula multiplies by 2 to account for the full circuit, out and back)
- CM = circular mil area of the wire, determined by the AWG gauge
The calculator tests each AWG gauge from 14 AWG (smallest) through 4/0 AWG (largest) and finds the smallest wire where the percent voltage drop stays at or below your specified maximum. This gives you the most cost-effective wire size that meets the voltage drop requirement.
Why wire sizing matters
Undersized wire causes excessive voltage drop, which leads to dimming lights, underperforming motors, and wasted energy as heat in the wire. The NEC recommends a maximum 3% voltage drop on branch circuits and 5% total from the service entrance to the farthest outlet. Choosing the correct wire gauge prevents these problems while avoiding the unnecessary cost of oversized conductors.
Copper vs. aluminum
Copper has a lower resistivity (12.9 ohm-cmil/ft) compared to aluminum (21.2 ohm-cmil/ft). For the same wire gauge and run length, aluminum produces approximately 64% more voltage drop than copper. When using aluminum conductors, you typically need to go up one or two wire sizes to match the performance of copper.
Worked example
For a 120V circuit with a 20A load and 50 feet of copper wire, with a 3% maximum voltage drop: The maximum allowable voltage drop is 120 x 0.03 = 3.6V. Starting with 14 AWG (4,110 CM): VD = (2 x 12.9 x 20 x 50) / 4,110 = 25,800 / 4,110 = 6.28V (5.23%). This exceeds 3%. Trying 12 AWG (6,530 CM): VD = 25,800 / 6,530 = 3.95V (3.29%). Still above 3%. Trying 10 AWG (10,380 CM): VD = 25,800 / 10,380 = 2.49V (2.07%). This is within the 3% limit. The recommended gauge is 10 AWG, with an estimated voltage drop of 2.49V and approximately 117.51V at the load.
CalculateY